Specifications Table for EHSX-D3 / ERGA04-08EVA

EHSX04P30DA3 / ERGA04EAV3A EHSX04P50DA3 / ERGA04EAV3A EHSX08P30DA3 / ERGA06EAV3A EHSX08P50DA3 / ERGA06EAV3A EHSX08P30DA3 / ERGA08EAV3A EHSX08P50DA3 / ERGA08EAV3A
Vnútorná jednotka EHSX04P30DA3 EHSX04P50DA3 EHSX08P30DA3 EHSX08P50DA3 EHSX08P30DA3 EHSX08P50DA3
Vykurovací výkon Men. kW 4.30, 4.60 4.30, 4.60 6.00, 5.90 6.00, 5.90 7.50, 7.80 7.50, 7.80
Chladiaci výkon Men. kW 4.86, 4.52 4.86, 4.52 5.96, 5.09 5.96, 5.09 6.25, 5.44 6.25, 5.44
Vstup napájania Kúrenie Men. kW 0.840, 1.26 0.840, 1.26 1.24, 1.69 1.24, 1.69 1.63, 2.23 1.63, 2.23
  Chladenie Men. kW 0.810, 1.36 0.810, 1.36 1.06, 1.55 1.06, 1.55 1.16, 1.73 1.16, 1.73
COP 5.10, 3.65 5.10, 3.65 4.85, 3.50 4.85, 3.50 4.60, 3.50 4.60, 3.50
EER 5.98, 3.32 5.98, 3.32 5.61, 3.28 5.61, 3.28 5.40, 3.14 5.40, 3.14
Ohrev teplej pitnej vody Všeobecné Uvedený záťažový profil   L XL L XL L XL
  Priemerná klíma Trieda energetickej účinnosti ohrevu vody   A+ A A+ A A+ A
Vykur. priestoru Priemerné podnebie – výstup vody 55°C Všeobecné SCOP   3.29 3.29 3.27 3.27 3.30 3.30
      Trieda sezónnej účinnosti vykurovania priestoru   A++ A++ A++ A++ A++ A++
  Priemerné podnebie – výstup vody 35°C Všeobecné SCOP   4.54 4.54 4.52 4.52 4.61 4.61
      Trieda sezónnej účinnosti vykurovania priestoru   A+++ A+++ A+++ A+++ A+++ A+++
Poznámky (1) - Stav 1: chladenie Ta 35 °C - LWE 18 °C (DT = 5 °C); kúrenie Ta DB/WB 7 °C/6 °C – LWC 35 °C (DT = 5 °C) (1) - Stav 1: chladenie Ta 35 °C - LWE 18 °C (DT = 5 °C); kúrenie Ta DB/WB 7 °C/6 °C – LWC 35 °C (DT = 5 °C) (1) - Stav 1: chladenie Ta 35 °C - LWE 18 °C (DT = 5 °C); kúrenie Ta DB/WB 7 °C/6 °C – LWC 35 °C (DT = 5 °C) (1) - Stav 1: chladenie Ta 35 °C - LWE 18 °C (DT = 5 °C); kúrenie Ta DB/WB 7 °C/6 °C – LWC 35 °C (DT = 5 °C) (1) - Stav 1: chladenie Ta 35 °C - LWE 18 °C (DT = 5 °C); kúrenie Ta DB/WB 7 °C/6 °C – LWC 35 °C (DT = 5 °C) (1) - Stav 1: chladenie Ta 35 °C - LWE 18 °C (DT = 5 °C); kúrenie Ta DB/WB 7 °C/6 °C – LWC 35 °C (DT = 5 °C)
  (2) - Stav 2: chladenie Ta 35 °C - LWE 7℃ (DT = 5 °C); kúrenie Ta DB/WB 7 °C/6 °C – LWC 45℃ (DT = 5 °C) (2) - Stav 2: chladenie Ta 35 °C - LWE 7℃ (DT = 5 °C); kúrenie Ta DB/WB 7 °C/6 °C – LWC 45℃ (DT = 5 °C) (2) - Stav 2: chladenie Ta 35 °C - LWE 7℃ (DT = 5 °C); kúrenie Ta DB/WB 7 °C/6 °C – LWC 45℃ (DT = 5 °C) (2) - Stav 2: chladenie Ta 35 °C - LWE 7℃ (DT = 5 °C); kúrenie Ta DB/WB 7 °C/6 °C – LWC 45℃ (DT = 5 °C) (2) - Stav 2: chladenie Ta 35 °C - LWE 7℃ (DT = 5 °C); kúrenie Ta DB/WB 7 °C/6 °C – LWC 45℃ (DT = 5 °C) (2) - Stav 2: chladenie Ta 35 °C - LWE 7℃ (DT = 5 °C); kúrenie Ta DB/WB 7 °C/6 °C – LWC 45℃ (DT = 5 °C)